    ANALISIS KESTABILAN PERALIHAN AKIBAT PELEPASAN BEBAN PADA SISTEM TENAGA LISTRIK PT. KPC SANGATTA MENGGUNAKAN METODE STATIC UNDER FREQUENCY LOAD SHEDDING --Ed.1

    19642049 / / /
    Politeknik Negeri Samarinda Samarinda 2023
    xvi;85 h ; 29 cm Bahasa:Ind

    ABSTRAK
    Iyang Mukti Ali Pembimbing
    19642049 I. Ipniansyah, S.T., M.T
    Program Studi Teknik Listrik II. Ir. Khairuddin Karim, S.T., M.T., I.P.M
    Analisis Kestabilan Peralihan Akibat Pelepasan Beban Pada Sistem Tenaga Listrik PT.
    KPC Sangatta Menggunakan Metode Static Under Frequency Load Shedding
    Penelitian dalam skripsi ini bertujuan menganalisis kestabilan peralihan terhadap
    respon frekuensi, tegangan, dan sudut rotor akibat pelepasan beban menggunakan metode
    static under frequency load shedding dan skema pelepasan beban yang ada di lapangan
    pada sistem tenaga listrik PT. KPC Sangatta, serta merancang pola mekanisme under
    frequency load shedding ketika terjadi gangguan besar pada generator yang keluar dari
    sistem. Metode penelitian menggunakan static under frequency load shedding dengan dua
    skenario gangguan berdasarkan lokasi terjadinya short circuit line to ground di node
    generator dimulai hitungan pada 1 detik pertama, kemudian pada hitungan 1,01 detik
    berikutnya CB terbuka yang berakibat generator keluar dari sistem dengan total waktu
    simulasi peralihan selama 20 detik.
    Hasil yang diperoleh pada masing-masing jenis mekanisme pelepasan beban yang
    berbeda, memiliki besaran yang sama untuk keseluruhan skenario gangguan. Berdasarkan
    respon frekuensi akibat pelepasan beban menggunakan metode static UFLS dan skema
    pelepasan beban dengan data setting stage-2 memiliki persamaan pada jumlah pelepasan
    beban sebesar 9,334 MW, namun yang membedakan pada waktu kestabilan frekuensi
    mencapai kondisi steady state di mana untuk metode static UFLS terjadi pada hitungan 7
    detik berikutmya, sedangkan skema data setting stage-2 terjadi pada hitungan 8,64 detik.
    Untuk skema pelepasan beban dengan data setting stage-1 tidak dapat mengembalikan
    frekuensi dengan handal di mana batas bawah frekuensi telah melewati standar. Sedangkan
    untuk kestabilan tegangan dan sudut rotor pada jenis mekanisme pelepasan bebannya
    memiliki hasil yang sama yaitu untuk tegangan dapat mencapai kondisi kestabilan steady-
    state sesuai standar yang diizinkan oleh PT. KPC Sangatta antara 0,95-1,05 p.u. Begitu
    pula untuk kestabilan sudut rotor mampu mencapai kondisi kestabilan steady-state
    tergantung dari skenario yang telah ditentukan.
    ABSTRACT
    Iyang Mukti Ali Mentor
    19642049 I. Ipniansyah, S.T., M.T
    Electrical Engineering Study Programme II. Ir. Khairuddin Karim, S.T., M.T., I.P.M
    Analysis of Transient Stability Due to Load Shedding in the Electric Power System of PT
    KPC Sangatta Using the Static Under Frequency Load Shedding Method.
    The research in this thesis aims to analyse the transient stability of frequency
    response, voltage, and rotor angle due to load shedding using static under frequency load
    shedding method and load shedding scheme in the field at KPC Sangatta PLTU system, as
    well as to design a pattern of under frequency load shedding mechanism when a major
    disturbance occurs in the generator out of the system. The research method uses static
    under frequency load shedding with two fault scenarios based on the location of the short
    circuit line to ground at the generator node starting at the count of the first 1 second, then
    at the count of the next 1.01 seconds the CB opens which results in the generator leaving
    the system with a total transient simulation time of 20 seconds.
    The results obtained for each different type of load shedding mechanism have the same
    magnitude for the entire fault scenario. Based on the frequency response due to load
    shedding using the static UFLS method and the load shedding scheme with stage-2 data
    setting has similarities in the amount of load shedding of 9.334 MW, but the difference is
    in the time of frequency stability to reach steady state conditions where for the static UFLS
    method occurs in the next 7 seconds, while the stage-2 data setting scheme occurs at a
    count of 8.64 seconds. For the load shedding scheme with stage-1 data setting, it cannot
    restore the frequency reliably where the lower limit of frequency has passed the standard.
    As for the stability of the voltage and rotor angle on the type of load shedding mechanism
    has the same results, namely for the voltage can achieve steady-state stability conditions
    according to the standards permitted by PT KPC Sangatta between 0.95-1.05 p.u.
    Similarly, for the stability of the angle of the rotor on the type of load shedding mechanism
    has the same results. Similarly, the rotor angle stability is able to achieve steady-state
    stability conditions depending on the scenario that has been determined