    ANALISIS LOSSES DAYA TERHADAP PERUBAHAN ARUS NETRAL PADA PENGHANTAR NETRAL AKIBAT KETIDAKSEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI GARDU INDUK TELUK PANDAN --Ed. 1

    Muhammad Mughni / / /
    SAMARINDA SAMARINDA 2021
    Viii; 175 h; ilus; 23 cm Bahasa:IND

    ABSTRACT
    Muhammad Mughni Advisor
    17642015 I. Ir. Khairuddin Karim, S.T.,M.T.
    Applied Bachelor Of Electrical Engineering II. IR. H. M. Syahrir Djalil, M.T.
    POWER LOSSES ANALYSIS OF CHANGES IN NEUTRAL CURRENT ON NEUTRAL
    TRANSFER DUE TO UNBALANCED LOAD ON DISTRIBUTION TRANSFORMERS AT
    TELUK PANDAN SUBSTATION
    Abstrack, load imbalances in the distribution network are often encountered, this is due
    to asynchronous ignition times, unbalanced connection of each phase, and neutral current.
    The magnitude of this neutral current depends on how big the load imbalance of the three
    phases is. The current flowing in this neutral conductor causes a power loss. At the Teluk
    Pandan Substation the imbalance occurs due to disturbances originating from fault
    currents of 1 phase to ground or 3 phase to ground. The calculation of the magnitude of
    the load imbalance that occurs due to disturbances in the Teluk Pandan Substation
    channel obtained the highest value on February 22, 2020 at 125.75% and the lowest value
    on September 11, 2020 at 1.86%. Calculation of the value of power losses due to neutral
    currents originating from load imbalances obtained the highest value for disturbance on
    22 February 2020 of 6105.44 watts and the lowest value on 11 September 2020 of 6.40
    watts. Power loss can be overcome by splitting the load or adding a new distribution
    transformer and monitoring the load on the distribution transformer to transfer the load
    from the R-S, S-T, and T-R phases. From the results of the research conducted, the results
    obtained exceed the current unbalance standard according to NEMA MG-1 with the
    results obtained exceeding 30% of the current unbalance.
    Keywords : neutral current, unbalance, power losses