Skripsi
#13455
SKR/TE 013 MUH a 2020 ISBN: 16 642 010

Subjects:Teknik Elektro PEMASANGAN FUSESAVER

    ANALISIS PENGARUH PEMASANGAN FUSESAVER TERHADAP KEANDALAN PENYULANG J4 GARDU INDUK KARANG JOANG BALIKPAPAN --

    MUHAMMAD CHAIRUL IMAN RANI / / /
    Samarinda 2020
    xix; 91 h; ilus; 23 cm Bahasa:Ind

    ABSTRAK
    Muhammad Chairul Iman Rani Pembimbing:
    16 642 010 I. Suratno, S.T., M.T.
    Program Studi Teknik Listrik D-IV II. Ir.H M. Syahrir Djalil, M.T.
    Analisis Pengaruh Pemasangan Fusesaver Terhadap Keandalan Penyulang J4 Gardu Induk
    Karang Joang Balikpapan
    Sistem distribusi merupakan sistem penyalur tenaga listrik yang langsung berhubungan dengan
    pelanggan. Dalam penyaluran energi listrik tidak menutup kemungkinan terjadinya gangguan yang
    akan mempengaruhi keandalan suatu sistem distribusi. Untuk menunjang keandalan penyulang J4
    maka dipasang alat pengaman fusesaver. Pada penelitian ini data yang digunakan adalah data rekap
    gangguan penyulang J4 sebelum dan sesudah pemasangan fusesaver. Data dianalisis dengan
    membandingkan nilai SAIFI dan nilai SAIDI sebelum dan sesudah pemasangan fusesaver. Hasil
    menunjukkan bahwa sebelum pemasangan fusesaver pelanggan penyulang J4 mengalami pemadaman
    sebesar 5.597478329 (kali/tahun) dan lama padam sebesar 10.50693617 (jam/tahun) dan setelah
    pemasangan fusesaver pelanggan penyulang J4 mengalami pemadaman sebesar 2.444891945
    (kali/tahun) dan lama padam sebesar 3.001103471 (jam/tahun). Dari hasil analisis pengaruh
    pemasangan fusesaver terhadap penyulang J4 dapat meningkatkan presentase keandalan nilai SAIDI
    sebesar 71,44% pertahun dan nilai SAIFI sebesar 56.32% pertahun. Pemasangan fusesaver dapat
    berpengaruh terhadap keandalan pada penyulang J4 Gardu Induk Karang Joang Balikpapan dengan
    meningkatkan presentase keandalan nilai SAIDI dan nilai SAIFI.
    Kata kunci: Fusesaver , Indeks Keandalan, SAIDI, SAIFI, Sistem distribusi.
    viii
    ABSTRACT
    Muhammad Chairul Iman Rani Pembimbing:
    16 642 010 I. Suratno, ST, MT
    Electrical Engineering Study Program D-IV II. Ir. H M.Syahrir Djalil, MT
    Analysis of the Effect of Fusesaver Installation on Reliability J4 Feeder at Karang Joang
    Balikpapan Substation
    The distribution system is a power distribution system that is directly related to customers. In the
    distribution of electrical energy, it is possible for disturbances to occur which will affect the reliability
    of a distribution system. To support the reliability of the J4 feeder, asafety device is installed
    fusesaver. In this study the data used were the recap data of J4 feeder disturbances before and
    afterinstallation fusesaver. Data were analyzed by comparing the SAIFI value and the SAIDI value
    before and afterinsertion fusesaver. The results showed that before the installation of the fusesaver, the
    J4 feeder customer experienced blackouts of 5,597478329 (times / year) and the duration of
    extinguishing was 10.50693617 (hours / year) and after the installation of the fusesaver, the J4 feeder
    customers experienced blackouts of 2.444891945 (times / year) and the duration of extinguishing was
    3.001103471 ( hour / year). From the results of the analysis of the effect ofinstallation fusesaver on J4
    feeders, the percentage of reliability of the SAIDI value was 71.44% per year and the SAIFI value was
    56.32% per year. The installation of a fusesaver can affect the reliability of the J4 feeder at Karang
    Joang Balikpapan Substation by increasing the percentage of the reliability of the SAIDI value and the
    SAIFI value.
    Keywords: Fusesaver, Reliability Index, SAIDI, SAIFI, Distribution system.